Rectangular duct system

Setoff

manufacturer: Akvilon | Kods: VKSSN

Rectangular Axis Offset

Product Description

Ventilation offset is a fitting designed to shift the axis of a rectangular duct without changing its flow cross-section. The item is used in places where a straight route installation is impossible: bypassing load-bearing beams, columns, intersecting with other engineering networks, or ceiling height differences.

Unlike makeshift solutions, the factory-made offset is calculated to maintain a constant free cross-sectional area throughout the bend. This prevents the creation of "bottlenecks," turbulence, and excess noise in the system.

Key Features and Ordering Parameters

  • Important when ordering: A rectangular duct has two sides (width and height), so when ordering, it is critical to specify not only the offset size (h) but also its direction relative to the airflow: offset up/down (height) or left/right (width).
  • Aerodynamics and length: There is a direct correlation: the larger the required offset (h), the longer the item length (L) must be. A transition that is too sharp creates air resistance. We select the length so that the slope angle is smooth and efficient.
  • Construction: The structure is reinforced with transverse beading (stiffening ribs). Assembly is performed on lock forming machines, ensuring seam tightness.
  • Materials: Z275 galvanized steel (standard), stainless steel (AISI 304/316), or powder coating in RAL colors.

Specifications and Dimensions

Below are the articles for standard cross-sections. For large offsets, the length is calculated individually.

Standard Parameters
Section (mm) Typical length L (mm) Article
100 x 100 400-600 VKSSN010010
200 x 200 400-600 VKSSN020020
300 x 300 400-600 VKSSN030030
400 x 400 600-800 VKSSN040040
500 x 500 600-800 VKSSN050050
600 x 600 600-800 VKSSN060060
700 x 700 600-800 VKSSN070070
800 x 800 600-800 VKSSN080080
900 x 900 800-1000 VKSSN090090
1000 x 1000 800-1000 VKSSN100100
 
Technical Data
Offset amount (h) Up to 500 mm (standard). >500 mm — individual calculation.
Metal thickness 0.5 – 0.9 mm (EN 1505)
Connection type Flange 20 mm, 30 mm, or 40 mm (depends on B size)
Production time Custom orders: 3–10 business days.

Installation Recommendations

  • Measurement accuracy: The item cannot be "adjusted" or trimmed on site. Carefully measure the distance between axes (h) on site before ordering.
  • Support: The offset shifts the route's center of gravity. Be sure to install additional suspensions (profile + threaded rod) immediately before and after the element to prevent flange skewing.
  • Sealing: Flange frames must be sealed with tape or sealant to prevent air leaks.

© 2012-2025 SIA "AKVILON"
e-mail: info@akvilon.lv | phone: +371 26336845, +371 20125412 | www.akvilon.eu | www.dumvadi.lv | e-shop - shop.akvilon.eu |